Boiler Settings

29th Dec 2025

  • Top cylinder 50° (controls final shutdown if boiler is out and no heat stored)
  • Top of dual stat (burner control) 82°
  • Bottom of dual stat below 70° return heat pump from accum
  • Overtemp pump start above 79° boost heat flow to accum

Both accumulator storage tank pumps reversed direction, System shut down changed to 50°

26th nov 2025

Grundfos UPM3 instructions

first lit on 24th

flow 1 1/2 turns opened to UFH in airing cupboard

Boiler circ pump (Laddomat) at no 2 after freeing from sludge starts about 60deg

  • Top cylinder 58° (controls final shutdown if boiler is out and no heat stored)
  • Top of dual stat (burner control) 83°
  • Bottom of dual stat below 74° return heat pump from accum
  • Overtemp pump start above 80° boost heat flow to accum

24th nov 2024

LAE MTC12 instructions ( to alter bottom one, alter top first , then reset)

Increased return heat stat from 62 to 70

Gas valve shut off up to 43

3 port valve actuator failed and removed

flow restricted to UFH in airing cupboard

4th Dec 2023

Stats needed for new box:

  • Top cylinder 51° (controls final shutdown if boiler is out and no heat stored)
  • Top of dual stat (burner control) 82°
  • Bottom of dual stat below 62° return heat pump from accum
  • Overtemp pump start above 80° boost heat flow to accum

21st March 2023

End of 2022 logs, last week

House set -back 15 ° on Gas 17° on wood

20th Feb

House 3 port valve and gas control set down to 36°

  • Top cylinder 51° (controls final shutdown if boiler is out and no heat stored)
  • Top of dual stat (burner control) 82°
  • Bottom of dual stat below 62° return heat from accum
  • Bottom cyl
  • Overtemp pump start (Top left stat) above 80° boost heat pump to accum
  • Mid cylinder (bottom right stat) stoke alarm disconnected

30 Jan 2023

disc usage 6,199.83

House 3 port valve and gas control set down to 36°

  • Top cylinder 51° (controls final shutdown if boiler is out and no heat stored)
  • Top of dual stat (burner control) 80°
  • Bottom of dual stat below 62° return heat from accum
  • Bottom cyl not needed
  • Overtemp pump start (Top left stat) above 78° boost heat to accum
  • Mid cylinder (bottom right stat) stoke alarm disconnected

20 Dec 2022

on vigas controller instuction P10 in the manual

  • max 225°
  • end 90°
  • fan 3
  • min fan3%
  • need to disable accum return pump after a cold start, (takes all heat out if boiler can’t maintain temperatre due to high demand)

Nov 21st 2022

  • Max water temp 75°
  • Max Flue 220°
  • Min flue now 90° (Shuts down boiler at the end of a cycle)
  • Min Fan 3%

Top stat now 60° shut down earlier

Bottom stat is now new pump to return heat from Accumulator pump on below 59°

Thermostat Settings 24th Feb 2022

  • Top cylinder 56° (controls final shutdown if boiler is out and no heat stored)
  • Mid cylinder (burner control) 79°
  • low cylinder(stoking needed alarm) 64°
  • Mid cylinder (Accumulator circ pump on) 74°
  • overtemp pump start (Top left stat) 78°
  • Bottom cylinder (bottom right stat) 60°

On boiler control panel:

  • Max water temp 75°
  • Max Flue 220°
  • Min flue 75° (Shuts down boiler at the end of a cycle)
  • Min Fan 3%
  • stopped rolling display
  • brightness 65%